Rehlko Engine Series

(60~227 kVA)

THREE-PHASE GENERATOR SETS
Specifications @1500rpm, 50Hz, 230-400V General Specifications
kVA Engine Alernator Unhoused Version(5)
Generator Set Model(1) Prime Power(3) Standby Power(4) Fuel Consumption 3/4 L/h Dimensions LxWxH,m Weight kg(6) Tank Capacity, L Data Sheet
KD66 60 66 12.8 KD39L04T-AW56* KH00811T 1.89 x 1.07 x 1.31 960 181 PDF
KD88 80 88 12.8 KD39L04T-AW56* KH00590T 1.89 x 1.07 x 1.31 1030 181 PDF
KD110 100 110 18 KD39L04T-AA56* KH00753T 1.89 x 1.07 x 1.31 1080 181 PDF
KD130 120 130
20.1 KD59L06T-AW56* KH01051T 2.15 x 1.10 x 1.53 1230 256 PDF
KD165 150 165 25 KD59L06T-AA56* KH01191T 2.15 x 1.10 x 1.53 1280 256 PDF
KD200 180 200 30 KD83L06T-AW56* KH01680T 2.50 x 1.10 x 1.64 1740 344 PDF
KD220 200 220 32 KD83L06T-AA56A* KH01681T 2.50 x 1.10 x 1.64 1760 344 PDF
KD250 227 250 37 KD83L06T-AA56B* KH01221T 2.50 x 1.10 x 1.64 1940 344 PDF

 

(1) Also available in the following voltages : 240/415 V, 220/380 V, 127/220 V, 115/220 V.
(2) Also available in the following voltages : 254/440 V, 127/220 V, 120/208 V.
(3) Prime power in direct current for an unlimited number of annual operating hours in variable load applications, in accordance with ISO8528, a 10% overload capacity is
     available for a period of 1 hour every 12-hours period of operation, in accordance with ISO3046-1.
(4) Emergency standby power available for supplying emergency power in variable load applications in accordance with ISO8528-1, no overload available for this service.
(5) The dimensions and weights apply to an unhoused generator set without options.
(6) Dry weight, without fuel.
(7) Also available in the following voltages :  220-240 V.
(8) 3000 rpm engine.