-Rated short circuit breaking current (kA) 20 - 25 - 31.5
-Rated duration of short circuit (s) 3
-Rated normal current (A) 630 - 800 - 1250
-1600 - 2000 - 2500
-Target application Building, industry, and power grid
Air-insulated Switchgear Panel ( F400 ) 1 to 40.5 kV
Electrical characteristics
Service voltage
kV
33
Rated voltage
kV
36
Rated insulation level (1mn)
kV rms
70
Peak withstand voltage (1.2/50μs)
kV peak
170
Frequency
Hz
50
Short time withstand current for:
- Switchboard
kA / s.
31,5/1
- Current transformer
kA / s.
31,5/1
Peak withstand current
kA peak
79
- Withdrawable SF6 circuit-breaker
-F400 switchgear has been specifically designed on the basis of that extensive experience.
- It also incorporates some very new solutions, giving the best in terms of continuity of service and operators’ safety.
Gas Insulated metal-enclosed Switchgear Panel (CBGS-0) 24 / 36 kV
- Up to 24/36 kV - 1250/1600/ 2000 A - 25/31.5 kA
- Continuity of service
- Optimised safety
- Easy installation and operation
- Investment optimisation
REL59802 Over Current/ Earth Fault Relay ( Sepam series 10 B41A)
Sepam series 10_REL59802
Sepam series 10 offers 3 types of digital overcurrent and earth fault protection devices for feeders and distribution transformers, each one dedicated to a single application.
Applications
Protection of secondary power distribution networks (MV/MV, MV/LV substations)
Protection of buildings with MV power supply (office buildings, shopping centers, industry, warehouses)